PanelDuct® Adaptor to Traditional Duct
In situations where PanelDuct® systems need to be connected to traditional sheetmetal duct systems, an adaptor plate is required to account for the step resulting form pre-insulation. This step is 35mm per side, external to the duct. Internally there is a smmoth transition, with no step.
- PD X = TD X + 70mm
- PD Y = TD Y + 70mm